# KNX Binding

The openHAB KNX binding allows to connect to KNX Home Automation (opens new window) installations. Switching lights on and off, activating your roller shutters, or changing room temperatures are only some examples.

To access your KNX bus, you either need a gateway device which is connected to the KNX bus and allows computers to access the bus communication. This can be either an Ethernet (as a Router or a Tunnel type) or a serial gateway. The KNX binding then can communicate directly with this gateway. Alternatively, a PC running KNXD (opens new window) (free open source component software) can be put in between which then acts as a broker allowing multiple clients to connect to the same gateway. Since the protocol is identical, the KNX binding can also communicate with it transparently.

Attention: With the introduction of Unit of Measurement (UoM) support, some data types have changed (see number channel below):

  • Data type for DPT 5.001 (Percent 8bit, 0 -> 100%) has changed from PercentType to QuantityTypefor number channels (dimmer, color, rollershutter channels stay with PercentType).
  • Data type for DPT 5.004 (Percent 8bit, 0 -> 255%) has changed from PercentType to QuantityType.
  • Data type for DPT 6.001 (Percent 8bit -128 -> 127%) has changed from PercentType to QuantityType.
  • Data type for DPT 9.007 (Humidity) has changed from PercentType to QuantityType.

Rules that check for or compare states and transformations that expect a raw value might need adjustments. If you run into trouble with that and need some time, you can disable UoM support on binding level via the disableUoM parameter. UoM are enabled by default and need to be disabled manually. A new setting is activated immediately without restart.

# Supported Things

The KNX binding supports two types of bridges, and one type of things to access the KNX bus. There is an ip bridge to connect to KNX IP Gateways, and a serial bridge for connection over a serial port to a host-attached gateway.

# Bridges

The following two bridge types are supported. Bridges don't have channels on their own.

# Discovery

KNX IP bridges, i.e. IP interfaces, routers, and knxd instances, are discovered through mulitcast communication in the local network. As a KNX setup is typically static, this in only done during startup of the binding. Corresponding bridges are added to the inbox. Additional configuration might be necessary after adding a bridge.

Note that several items per device might be created, as routers typically support routing and tunneling. Make sure you import only one item per device.

Discovery is not available for serial bridges and device Things described below. Discovery of IP bridges will not work without further measures if openHAB and the interface run on different network segments, as multicast traffic is typically not forwarded.

# IP Gateway

The IP Gateway is the most commonly used way to connect to the KNX bus. At its base, the ip bridge accepts the following configuration parameters:

Name Required Description Default value
type Yes The IP connection type for connecting to the KNX bus (TUNNEL, ROUTER, SECURETUNNEL or SECUREROUTER) -
ipAddress for TUNNEL Network address of the KNX/IP gateway. If type ROUTER is set, the IPv4 Multicast Address can be set. for TUNNEL: <nothing>, for ROUTER: 224.0.23.12
portNumber for TUNNEL Port number of the KNX/IP gateway 3671
localIp No Network address of the local host to be used to set up the connection to the KNX/IP gateway the system-wide configured primary interface address
localSourceAddr No The (virtual) individual address for identification of this openHAB Thing within the KNX bus

Note: Use a free address, not the one of the interface. Or leave it at 0.0.0 and let openHAB decide which address to use. When using knxd, make sure not to use one of the addresses reserved for tunneling clients.
0.0.0
useNAT No Whether there is network address translation between the server and the gateway false
readingPause No Time in milliseconds of how long should be paused between two read requests to the bus during initialization 50
responseTimeout No Timeout in seconds to wait for a response from the KNX bus 10
readRetriesLimit No Limits the read retries while initialization from the KNX bus 3
autoReconnectPeriod No Seconds between connect retries when KNX link has been lost (0 means never). 0
routerBackboneKey No KNX secure: Backbone key for secure router mode -
tunnelUserId No KNX secure: Tunnel user id for secure tunnel mode (if specified, it must be a number >0) -
tunnelUserPassword No KNX secure: Tunnel user key for secure tunnel mode -
tunnelDeviceAuthentication No KNX secure: Tunnel device authentication for secure tunnel mode -

# Serial Gateway

The serial bridge accepts the following configuration parameters:

Name Required Description Default value
serialPort Y The serial port to use for connecting to the KNX bus -
readingPause N Time in milliseconds of how long should be paused between two read requests to the bus during initialization 50
responseTimeout N Timeout in seconds to wait for a response from the KNX bus 10
readRetriesLimit N Limits the read retries while initialization from the KNX bus 3
autoReconnectPeriod N Seconds between connect retries when KNX link has been lost, 0 means never retry 0
useCemi N Use newer CEMI message format, useful for newer devices like KNX RF sticks, kBerry, etc. false

# Things

# device Things

basic Things are wrappers around arbitrary group addresses on the KNX bus. They have no specific function in the KNX binding, except that if the address is defined, the binding will actively poll the Individual Address on the KNX bus to detect that the KNX actuator is reachable. Under normal real-world circumstances, either all devices on a bus are reachable, or the entire bus is down. If line couplers are installed, physical device addressing might be filtered; in this case, please do not specify the addresses for devices on this line. When fetch is set to true, the binding will read out the memory of the KNX actuator in order to detect configuration data and so forth. This is just for information and has no effect on the functionality of the binding. It can safely be turned off to save bandwidth on the bus or avoid problems with older devices.

Name Required Description Default value
address N The individual device address (in 0.0.0 notation) -
fetch N Read out the device parameters and address/communication object tables (requires the address) false
pingInterval N Interval (in seconds) to contact the device and set the thing status based on the result (requires the address) 600
readInterval N Interval (in seconds) to actively request reading of values from the bus (0 if they should only be read once at startup) 0

Different kinds of channels are defined and can be used to group together Group Addresses. All channels of a device share one configuration parameter defined at the device level: readInterval, an optional parameter that indicates if the 'readable' group addresses of that Channel should be read periodically at the given interval, in seconds. 'Readable' group addresses are marked with an < in the group address definition of a Channel, see below. All readable group addresses are queried by openHAB during startup. If readInterval is not specified or set to 0, no further periodic reading will be triggered (default: 0).

# Channel Types

Standard channels are used most of the time. They are used in the common case where the physical state is owned by a device within the KNX bus, e.g., by a switch actuator that "knows" whether the light is turned on or off, or by a temperature sensor that reports the room temperature regularly.

Control channel types (suffix -control) are used for cases where the KNX bus does not own the physical state of a device. This could be the case if, for example, a lamp from another binding should be controlled by a KNX wall switch. When a GroupValueRead telegram is sent from the KNX bus to a *-control Channel, the bridge responds with a GroupValueResponse telegram to the KNX bus.

# Channel Type color, color-control
Parameter Description Default DPT
hsb Group address for the color 232.600
switch Group address for the binary switch 1.001
position Group address brightness 5.001
increaseDecrease Group address for relative brightness 3.007

The hsb address supports DPT 232.600 (RGB), 242.600 (xyY), and 251.600 (RGBW).

Some RGB/RGBW products (e.g. MDT) use HSB values for DPT 232.600 instead of RGB. This is supported as "vendor-specific DPT" with a value of 232.60000.

RGBW (DPT 251.600) can either be converted to HSBType, or represented by two items: a HSBType for RGB and an additional PercentType for the W channel. Default handling for RGBW is to use separate items. Note that this also requires two frames to be sent out separately when these elements are sent to the bus, as the binary representation uses a partially populated KNX frame. Alternatively, a single HSB item can be used. Conversion to a single HSBType will lose the exact setting for W, and will reconstruct it when a conversion to RGBW is required. This option can be selected using the special DPT 251.60600.

# Channel Type contact, contact-control
Parameter Description Default DPT
ga Group address 1.009

Attention: Due to a bug in the original implementation, the states for DPT 1.009 are inverted (i.e., 1 is mapped to OPEN instead of CLOSE). A change would break all existing installations and is therefore not implemented.

# Channel Type datetime, datetime-control
Parameter Description Default DPT
ga Group address 19.001
# Channel Type dimmer, dimmer-control
Parameter Description Default DPT
switch Group address for the binary switch 1.001
position Group address of the absolute position 5.001
increaseDecrease Group address for relative movement 3.007
# Channel Type number, number-control
Parameter Description Default DPT
ga Group address 9.001

Note: The number channel has full support for Units Of Measurement (UoM).

Using the UoM feature of openHAB (QuantityType) requires that the DPT value is set correctly. Automatic type conversion will be applied if required.

Incoming values from the KNX bus are converted to values with units (e.g. 23 °C). If the channel is linked to the correct item-type (Number:Temperature in this case), the display unit can be controlled by item metadata (e.g., %.1f °F for 1 digit of precision in Fahrenheit). The unit is stripped if the channel is linked to a plain number item (type Number).

Outgoing values with unit are first converted to the unit associated with the DPT (e.g., a value of 10 °F is converted to -8.33 °C if the channel has DPT 9.001). Values from plain number channels are sent as-is (without any conversion).

# Channel Type rollershutter, rollershutter-control
Parameter Description Default DPT
upDown Group address for relative movement 1.008
stopMove Group address for stopping 1.010
position Group address for the absolute position 5.001
# Channel Type string, string-control
Parameter Description Default DPT
ga Group address 16.001
# Channel Type switch, switch-control
Parameter Description Default DPT
ga Group address for the binary switch 1.001

# Control Channel Types

In contrast to the standard channels above, the control channel types are used for cases where the KNX bus does not own the physical state of a device. This could, for example, be the case if a lamp from another binding should be controlled by a KNX wall switch. When a GroupValueRead telegram is sent from the KNX bus to a *-control Channel, the bridge responds with a GroupValueResponse telegram to the KNX bus.

# Channel Type "switch-control"
Parameter Description Default DPT
ga Group address for the binary switch 1.001
# Channel Type "dimmer-control"
Parameter Description Default DPT
switch Group address for the binary switch 1.001
position Group address of the absolute position 5.001
increaseDecrease Group address for relative movement 3.007
frequency Increase/Decrease frequency in milliseconds in case the binding should handle that (0 if the KNX device sends the commands repeatedly itself) 0
# Channel Type "rollershutter-control"
Parameter Description Default DPT
upDown Group address for relative movement 1.008
stopMove Group address for stopping 1.010
position Group address for the absolute position 5.001
# Channel Type "contact-control"
Parameter Description Default DPT
ga Group address 1.009

Attention: Due to a bug in the original implementation, the states for DPT 1.009 are inverted (i.e. 1 is mapped to OPEN instead of CLOSE). A change would break all existing installations and is therefore not implemented.

# Channel Type "number-control"
Parameter Description Default DPT
ga Group address 9.001

For UoM support, see the explanations of the number channel.

# Channel Type "string-control"
Parameter Description Default DPT
ga Group address 16.001
# Channel Type "datetime-control"
Parameter Description Default DPT
ga Group address 19.001

# Group Address Notation

<config>="[<dpt>:][<|>]<mainGA>[[+[<]<listeningGA>][+[<]<listeningGA>..]]"

where parts in brackets [] denote optional information.

Each configuration parameter has a mainGA where commands are written to and optionally several listeningGAs.

mainGA also listens to incoming packets, unless prefixed with a > character. This is recommended if you have a dedicated status group address which is added as listeningGA.

The optional < sign tells whether the group address of the datapoint accepts read requests on the KNX bus (it does, if the sign is there). The group addresses marked with < are read by openHAB during startup. Future versions might support reading from one GA only. With *-control channels, the state is not owned by any device on the KNX bus, therefore no read requests will be sent by the binding, i.e. < signs will be ignored for them.

The element dpt is highly recommended and may change to a mandatory element in future versions. If omitted, the corresponding default value will be used (see the channel descriptions above).

# Mapping DPTs to openHAB Types

Datapoint Types (DPTs) define how the content of a KNX telegram is interpreted.

The following table is a complete list of DPTs currently supported by openHAB. OpenHAB supports all DPTs supported by the corresponding release of the Calimero library, plus a few specific additions.

The default mapping is given, however DPTs can be overwritten. KNX frames do not contain information about the encoding or DPT, so any DPT with a compatible byte size and a useful encoding can be used. A good example for this are bitfields represented as String which are mapped to a DPT of DecimalType for handling in rules. For more details, see the KNX specification (section 3.7.2, System Specifications, Interworking, Datapoint Types).

In case a missing DPT or subtype is needed, there is a good chance that a DPT of matching size and DecimalType is found. Further DPTs and subtypes may be added later once implemented and released in the Calimero library (opens new window).

DPT Primary openHAB type (things) (items with UOM) Remark
1.001-1.007 OnOffType (switch), OpenClosedType (contact)
1.008 UpDownType (e.g. for dimmer, rollershutter)
1.009 OnOffType (switch), OpenClosedType (contact) Not according to spec, see above
1.010 StopMoveType (e.g. for rollershutter)
1.011-1.016 OnOffType (switch), OpenClosedType (contact)
1.017 OnOffType (switch), OpenClosedType (contact) Trigger, use states OFF or CLOSED
1.018-1.019 OnOffType (switch), OpenClosedType (contact)
1.021 OnOffType (switch), OpenClosedType (contact)
1.022 DecimalType (number) Counting from 0, use DPT if you need a DecimalType
1.023-1.024 OnOffType (switch), OpenClosedType (contact)
1.100 OnOffType (switch), OpenClosedType (contact)
1.1200-1.1201 OnOffType (switch), OpenClosedType (contact)
2.001-2.012 DecimalType (number)
3.007 IncreaseDecreaseType (e.g. dimmer)
3.008 UpDownType (e.g. rollershutter)
5.001 QuantityType<> (number) (Number:Percent) Alternatively: PercentType
5.003 QuantityType<> (number) (Number:Angle)
5.004 QuantityType<> (number) (Number:Percent) 0-255%, no mapping to PercentType
5.005 DecimalType (number)
5.006 DecimalType (number) 255 is reserved
5.010 DecimalType (number)
6.001 QuantityType<> (number) (Number:Percent) -128..127%, no mapping to PercentType
6.010 DecimalType (number) -128..127
6.020 StringType (string) Override with DPT5.010 if you need DecimalType
7.001 DecimalType (number)
7.002-7.007 QuantityType<> (number) (Number:Time)
7.010 DecimalType (number)
7.011 QuantityType<> (number) (Number:Length)
7.012 QuantityType<> (number) (Number:ElectricCurrent)
7.013 QuantityType<> (number) (Number:Length)
7.600 QuantityType<> (number) (Number:Temperature)
8.001 DecimalType (number)
8.002-7.007 QuantityType<> (number) (Number:Time)
8.010 QuantityType<> (number) (Number:Percent)
8.011 QuantityType<> (number) (Number:Angle)
8.012 QuantityType<> (number) (Number:Length)
9.xxx (opens new window) QuantityType<> (number) (Number:...) See documentation on UOM (opens new window)
9.001 QuantityType<> (number) (Number:...) Lower values than absolute zero will be set to -273 °C
9.002-9.003 QuantityType<> (number) (Number:...)
9.004-9.008 QuantityType<> (number) (Number:...) No negative values allowed
9.009-9.011 QuantityType<> (number) (Number:...)
9.020-9.027 QuantityType<> (number) (Number:...)
9.027-9.030 QuantityType<> (number) (Number:...) No negative values allowed
10.001 DateTimeType (datetime) Time. Date is set to 1/Jan/1970 + ofs if weekday is given. KNX can represent year 1990..2089.
11.001 DateTimeType (datetime) Date only.
12.001 DecimalType (number)
12.100-12.102 QuantityType<> (number) (Number:Time)
12.1200-12.1201 QuantityType<> (number) (Number:Volume)
13.xxx (opens new window) QuantityType<> (number) (Number:...) See documentation on UOM (opens new window)
13.001 DecimalType (number)
13.002 QuantityType<> (number) (Number:VolumetricFlowRate)
13.010-13.016 QuantityType<> (number) (Number:...)
13.100 QuantityType<> (number) (Number:...)
13.1200-13.1201 QuantityType<> (number) (Number:Time)
14.xxx (opens new window) QuantityType<> (number) (Number:...) See documentation on UOM (opens new window)
14.000-14.080 QuantityType<> (number) (Number:...)
14.1200-14.1201 QuantityType<> (number) (Number:...)
16.000 StringType (string) ASCII
16.001 StringType (string) ISO 8859-1
17.001 DecimalType (number) Scene 0..63
18.001 DecimalType (number) Scene 0..63, add offset 0x80 (128) for storing scenes
19.001 DateTimeType (datetime) (DateTime) Date and Time, year can be 1900..2155
20.xxx (opens new window) Incomplete, only subtypes given below are supported; override with DPT5.010 if you need enum as DecimalType
20.001-20.009 StringType (string)
20.011-20.014 StringType (string)
20.017 StringType (string)
20.020-20.021 StringType (string)
20.100-20.114 StringType (string)
20.120-20.122 StringType (string)
20.600-20.610 StringType (string)
20.801-20.804 StringType (string)
20.1000-20.1005 StringType (string)
20.1200 StringType (string)
20.1202 StringType (string)
21.xxx (opens new window) Incomplete, only subtypes given below are supported; override with DPT5.010 if you need bitset as DecimalType
21.001-20.002 StringType (string)
21.100-20.106 StringType (string)
21.601 StringType (string)
21.1000-21.1002 StringType (string)
21.1010 StringType (string)
22.xxx (opens new window) Incomplete, only subtypes given below are supported; override with DPT7.010 if you need bitset as DecimalType
22.101 StringType (string)
22.1000 StringType (string)
28.001 StringType (string) KNX representation is Null-terminated, do not include null characters
29.010-29.012 QuantityType<> (number) (Number:...)
229.001 DecimalType (number) Scaling coded in KNX frame is regarded; for sending always encoded with flag "dimensionless"
232.600 HSBType (color) RGB
232.60000 HSBType (color) Non-Standard, DPT 232.600 with HSB instead of RGB data
235.001 QuantityType<> (number) (Number:ActiveEnergy) Composed DPT 235.001, first element ActiveEnergy (Wh), read only
235.61001 DecimalType (number) Non-Standard, composed DPT 235.001, second element Tariff (plain number), read only
242.600 HSBType (color) xyY
243.600 StringType (string)
249.600 StringType (string)
250.600 StringType (string)
251.600 HSBType (color) RGBW, RGB part as HSBType
251.600 PercentType RGBW, W part separately for Dimmer
251.60600 HSBType (color) Non-Standard, lossy conversion from HSBType to RGBW
252.600 StringType (string)
253.600 StringType (string)
254.600 StringType (string)

# Special DPTs

OpenHAB supports all DPTs supported by the corresponding release of the Calimero library.

Additional DPTs have been introduced to add functionality:

DPT Description Remark
DPT 232.60000 DPT 232.600 with HSB instead of RGB data (see below) read/write
DPT 235.001 Composed DPT 235.001, first element ActiveEnergy (Wh) read only
DPT 235.61001 Composed DPT 235.001, second element Tariff (plain number) read only

# KNX Secure

NOTE: Support for KNX Secure is partly implemented for openHAB and should be considered as experimental.

# KNX IP Secure

KNX IP Secure protects the traffic between openHAB and your KNX installation. It requires a KNX Secure Router or a Secure IP Interface and a KNX installation with security features enabled in the ETS tool.

For Secure routing mode, the so-called backbone key needs to be configured in openHAB. It is created by the ETS tool and cannot be changed via the ETS user interface.

  • The backbone key can be extracted from Security report (ETS, Reports, Security, look for a 32-digit key) and specified in parameter routerBackboneKey.

For Secure tunneling with a Secure IP Interface (or a router in tunneling mode), more parameters are required. A unique device authentication key, and a specific tunnel identifier and password need to be available.

  • All information can be looked up in ETS and provided separately: tunnelDeviceAuthentication, tunnelUserPassword. tunnelUserId is a number that is not directly visible in ETS, but can be looked up in keyring export or deduced (typically 2 for the first tunnel of a device, 3 for the second one, ...). tunnelUserPasswort is set in ETS in the properties of the tunnel (below the IP interface, you will see the different tunnels listed) and denoted as "Password". tunnelDeviceAuthentication is set in the properties of the IP interface itself; check for the tab "IP" and the description "Authentication Code".

# KNX Data Secure

KNX Data Secure protects the content of messages on the KNX bus. In a KNX installation, both classic and secure group addresses can coexist. Data Secure does not necessarily require a KNX Secure Router or a Secure IP Interface, but a KNX installation with newer KNX devices that support Data Secure and with security features enabled in the ETS tool.

NOTE: openHAB currently ignores messages with secure group addresses.

# Examples

The following two templates are sufficient for almost all purposes. Only add parameters to the Bridge and Thing configuration if you know exactly what functionality it is needed for.

# Type ROUTER mode configuration Template

knx.things:

Bridge knx:ip:bridge [
    type="ROUTER",
    autoReconnectPeriod=60 //optional, do not set <30 sec.
] {
    Thing device knx_device "knx_device_name" @ "knx_device_group" [
        //readInterval=3600 //optional, only used if reading values are present
    ] {
        //Items configurations
    }
}

# Type TUNNEL mode configuration Template

knx.things:

Bridge knx:ip:bridge [
    type="TUNNEL",
    ipAddress="192.168.0.111",
    autoReconnectPeriod=60 //optional, do not set <30 sec.
] {
    Thing device knx_device "knx_device_name" @ "knx_device_group" [
        //readInterval=3600 //optional, only used if reading values are present
    ] {
        //Items configurations
    }
}

# Full Example

//TUNNEL
Bridge knx:ip:bridge [
    type="TUNNEL",
    ipAddress="192.168.0.10",
    portNumber=3671,
    localIp="192.168.0.11",
    readingPause=50,
    responseTimeout=10,
    readRetriesLimit=3,
    autoReconnectPeriod=60,
    localSourceAddr="0.0.0"
] {
    Thing device generic [
        address="1.2.3",
        fetch=true,
        pingInterval=300,
        readInterval=3600
    ] {
        Type switch        : demoSwitch        "Light"       [ ga="3/0/4+<3/0/5" ]
        Type color         : demoColorLight    "Color"       [ hsb="6/0/10+<6/0/11", switch="6/0/12+<6/0/13", position="6/0/14+<6/0/15", increaseDecrease="6/0/16+<6/0/17" ]
        Type rollershutter : demoRollershutter "Shade"       [ upDown="4/3/50+4/3/51", stopMove="4/3/52+4/3/53", position="4/3/54+<4/3/55" ]
        Type contact       : demoContact       "Door"        [ ga="1.019:<5/1/2" ]
        Type number        : demoTemperature   "Temperature" [ ga="9.001:<5/0/0" ]
        Type dimmer        : demoDimmer        "Dimmer"      [ switch="5/0/0", position="5/0/2+<5/0/3", increaseDecrease="5/0/4" ]
        Type string        : demoString        "Message"     [ ga="5/3/1" ]
        Type datetime      : demoDatetime      "Alarm"       [ ga="5/5/42" ]
    }
}

//ROUTER
Bridge knx:ip:bridge [
    type="ROUTER",
    ipAddress="224.0.23.12",
    portNumber=3671,
    localIp="192.168.0.11",
    readingPause=50,
    responseTimeout=10,
    readRetriesLimit=3,
    autoReconnectPeriod=60,
    localSourceAddr="0.0.0"
] {}

knx.items:

Switch              demoSwitch         "Light [%s]"               <light>          { channel="knx:device:bridge:generic:demoSwitch" }
Color               demoColorLight     "Color [%s]"               <light>          { channel="knx:device:bridge:generic:demoColorLight" }
Dimmer              demoDimmer         "Dimmer [%d %%]"           <light>          { channel="knx:device:bridge:generic:demoDimmer" }
Rollershutter       demoRollershutter  "Shade [%d %%]"            <rollershutter>  { channel="knx:device:bridge:generic:demoRollershutter" }
Contact             demoContact        "Front Door [%s]"          <frontdoor>      { channel="knx:device:bridge:generic:demoContact" }
Number:Temperature  demoTemperature    "Temperature [%.1f °C]"    <temperature>    { channel="knx:device:bridge:generic:demoTemperature" }
String              demoString         "Message of the day [%s]"                   { channel="knx:device:bridge:generic:demoString" }
DateTime            demoDatetime       "Alarm [%1$tH:%1$tM]"                       { channel="knx:device:bridge:generic:demoDatetime" }

knx.sitemap:

sitemap knx label="KNX Demo Sitemap" {
  Frame label="Demo Elements" {
    Switch      item=demoSwitch
    Slider      item=demoDimmer
    Colorpicker item=demoColorLight
    Default     item=demoRollershutter
    Text        item=demoContact
    Text        item=demoTemperature
    Text        item=demoString
    Text        item=demoDatetime
  }
}

# Control Example

control.things:

Bridge knx:serial:bridge [
    serialPort="/dev/ttyAMA0",
    readingPause=50,
    responseTimeout=10,
    readRetriesLimit=3,
    autoReconnectPeriod=60
] {
    Thing device generic {
        Type switch-control        : controlSwitch        "Control Switch"        [ ga="3/3/10+<3/3/11" ]   // '<'  signs are allowed but will be ignored for control Channels
        Type dimmer-control        : controlDimmer        "Control Dimmer"        [ switch="3/3/50+3/3/48", position="3/3/46", increaseDecrease="3/3/49", frequency=300 ]
        Type color                 : controlColorLight    "Color"                 [ hsb="6/0/10", switch="6/0/12", position="6/0/14", 
        Type rollershutter-control : controlRollershutter "Control Rollershutter" [ upDown="3/4/1+3/4/2", stopMove="3/4/3", position="3/4/4" ]
        Type number-control        : controlNumber        "Control Number"        [ ga="1/2/2" ]
        Type string-control        : controlString        "Control String"        [ ga="1/4/2" ]
        Type datetime-control      : controlDatetime      "Control Datetime"      [ ga="5/1/30" ]
    }
}

Bridge hue:bridge:bridge "Philips Hue Bridge" [
    ipAddress="...",
    userName="..."
] {
    Thing 0210 1 "Color Lamp" [ lightId="1" ]
}

knx.items:

Switch        demoSwitch         "Light [%s]"               <light>          { channel="hue:0210:bridge:1:color", channel="knx:device:bridge:generic:controlSwitch" }
Dimmer        demoDimmer         "Dimmer [%d %%]"           <light>          { channel="hue:0210:bridge:1:color", channel="knx:device:bridge:generic:controlDimmer" }

# Console Commands

The KNX binding provides additional functionality which can be triggered from the openHAB console. Type openhab:knx on the openHAB console for further information.