Skip to content

myVAILLANT Binding ​

This binding connects Vaillant heating systems (e.g. aroTHERM plus heat pumps) with a sensoCOMFORT controller (VRC720) to openHAB through the myVAILLANT cloud, the backend of the myVAILLANT app. The API client is based on myPyllant.

Limitations ​

  • Only systems with the control identifier tli (sensoCOMFORT VRC720 with a VR920/VR921/VR940f gateway) are supported. Systems with a VRC700 (vrc700) or iQconnect (scf) controller go offline with a configuration error.
  • ambiSENSE rooms, ventilation units and EEBUS are not supported. Time programs can be read and written as JSON with the actions.
  • Vaillant limits the number of requests per account (call volume quota). When it is exceeded, the API answers with Out of call volume quota for up to an hour and the binding pauses all requests until then. All clients of an account share the quota, e.g. the myVAILLANT app and other integrations.

Supported Things ​

Thing TypeDescription
accountBridge for the myVAILLANT account, logs in and pauses requests while the quota is exceeded
systemBridge for one system (a home in the app), reads the whole system in one update
zoneA zone (rooms controlled together)
circuitA heating circuit with flow temperature and heating curve
dhwDomestic hot water
deviceA device of the system, e.g. the heat pump or the electric backup heater

Discovery ​

After adding the account bridge, its systems appear in the inbox. After adding a system bridge, its zones, circuits, hot water and devices appear in the inbox. Discovery uses the data of the regular updates and causes (almost) no additional requests.

Thing Configuration ​

account Bridge ​

NameTypeDescriptionDefaultRequiredAdvanced
usernametextEmail address of the myVAILLANT accountN/Ayesno
passwordtextPassword of the accountN/Ayesno
brandtextvaillant, sdbg (Saunier Duval), bulex, glow-worm or demirdokumvaillantyesno
countrytextCountry of the account (Vaillant and Saunier Duval) in lower case letters, e.g. germany, austria, unitedkingdomgermanynono
refreshIntervalintegerSeconds between updates of the systems (at least 60)300nono
energyRefreshIntervalintegerMinutes between updates of today's energy values, 0 disables them60nono
fetchRtsbooleanRead operation time and on/off cycles of the devices (one request per update)falsenono
fetchMpcbooleanRead the current power of the devices (one request per update)falsenono
fetchConnectionStatusbooleanRead whether the system is online (one request per update)falsenoyes
fetchTroubleCodesbooleanRead the diagnostic trouble codes (one request per update)falsenoyes
refreshDelayintegerSeconds to wait after a command before updating, the API takes a while to show new values10noyes
quickVetoDurationInHoursdecimalHours a temperature set outside of manual mode (quick veto) lasts3nono
holidayDurationInDaysintegerDays away mode lasts when switched on without an end365noyes
manualCoolingDurationInDaysintegerDays manual cooling lasts when switched on without an end30noyes

Each update of a system costs two requests (system state, and the device list at most every 30 minutes) plus one for each fetch... option. Energy values cost one request per linked energy channel and update.

system Bridge ​

NameTypeDescriptionRequired
systemIdtextID of the system, filled in by discoveryyes

zone, circuit and dhw Things ​

NameTypeDescriptionRequired
indexintegerIndex of the zone or circuit (the first one is 0), hot water usually has index 255yes

device Thing ​

NameTypeDescriptionRequired
deviceUuidtextID of the device, filled in by discoveryyes

Channels ​

account ​

ChannelTypeRead/WriteDescription
api-requestsNumberRRequests sent to Vaillant today (advanced)

system ​

ChannelTypeRead/WriteDescription
outdoor-temperatureNumber:TemperatureROutdoor temperature
outdoor-temperature-average-24hNumber:TemperatureRAverage outdoor temperature of the last 24 hours
water-pressureNumber:PressureRWater pressure of the system
system-flow-temperatureNumber:TemperatureRFlow temperature of the system
cylinder-temperature-top-dhwNumber:TemperatureRTop temperature of the hot water cylinder
cylinder-temperature-bottom-dhwNumber:TemperatureRBottom temperature of the hot water cylinder
cylinder-temperature-top-chNumber:TemperatureRTop temperature of the heating buffer
cylinder-temperature-bottom-chNumber:TemperatureRBottom temperature of the heating buffer
energy-manager-stateStringRSTANDBY, HEATING, DHW or COOLING
system-offSwitchRWhether the system is switched off
holidaySwitchRWAway mode, ON starts it now for holidayDurationInDays days
holiday-startDateTimeRWStart of away mode
holiday-endDateTimeRWEnd of away mode
manual-coolingSwitchRWCooling for days, ON starts it now for manualCoolingDurationInDays days
manual-cooling-startDateTimeRStart of manual cooling
manual-cooling-endDateTimeRWEnd of manual cooling
ventilation-boostSwitchRWVentilation boost
heating-energy-efficiencyNumberRHeat generated per consumed electrical energy for heating today, all devices
firmware-update-requiredSwitchRWhether a firmware update is required
onlineSwitchRWhether the system is connected (needs fetchConnectionStatus)
trouble-codesStringRDiagnostic trouble codes (needs fetchTroubleCodes)
has-trouble-codesSwitchRWhether there are trouble codes (needs fetchTroubleCodes)
last-updateDateTimeRTime of the last successful update (advanced)

zone ​

ChannelTypeRead/WriteDescription
current-room-temperatureNumber:TemperatureRRoom temperature measured by the controller
current-room-humidityNumber:DimensionlessRHumidity measured by the controller
desired-room-temperature-setpointNumber:TemperatureRWCurrent target temperature, a command sets the manual mode setpoint in manual mode, else a quick veto
desired-room-temperature-setpoint-heatingNumber:TemperatureRCurrent target temperature for heating
desired-room-temperature-setpoint-coolingNumber:TemperatureRCurrent target temperature for cooling
operation-mode-heatingStringRWTIME_CONTROLLED, MANUAL or OFF
operation-mode-coolingStringRWTIME_CONTROLLED, MANUAL or OFF
manual-mode-setpoint-heatingNumber:TemperatureRWTarget temperature in manual mode
setpoint-coolingNumber:TemperatureRWTarget temperature for cooling
set-back-temperatureNumber:TemperatureRWTemperature outside of the time windows in time controlled mode
heating-stateStringRIDLE, HEATING_UP or COOLING_DOWN
current-special-functionStringRNONE, QUICK_VETO, HOLIDAY, SYSTEM_OFF, VENTILATION_BOOST or ONE_DAY_BANK_HOLIDAY
hvac-actionStringRidle, heating or cooling, the state of the zone's circuit
quick-vetoSwitchRWQuick veto, ON starts it with the manual mode setpoint for quickVetoDurationInHours hours
quick-veto-endDateTimeREnd of the quick veto
quick-veto-durationNumber:TimeRWRemaining time of the quick veto, a command sets a new duration
manual-cooling-activeSwitchRWhether manual cooling is active

circuit ​

ChannelTypeRead/WriteDescription
circuit-stateStringRHEATING, COOLING or STANDBY
current-flow-temperatureNumber:TemperatureRCurrent flow temperature
flow-temperature-setpointNumber:TemperatureRTarget flow temperature
heating-curveNumberRWSlope of the heating curve
heat-demand-limited-by-outside-temperatureNumber:TemperatureRWNo heat demand above this outdoor temperature
min-flow-temperature-setpointNumber:TemperatureRWMinimum flow temperature
max-flow-temperature-setpointNumber:TemperatureRMaximum flow temperature
room-temperature-control-modeStringRInfluence of the room temperature, e.g. NON (advanced)
calculated-energy-manager-stateStringRState of the energy manager for the circuit (advanced)
cooling-allowedSwitchRWhether the circuit may cool

dhw ​

ChannelTypeRead/WriteDescription
current-temperatureNumber:TemperatureRTemperature of the hot water
tapping-setpointNumber:TemperatureRWTarget temperature, whole degrees
operation-modeStringRWTIME_CONTROLLED, MANUAL or OFF
current-special-functionStringRREGULAR, CYLINDER_BOOST, HOLIDAY or SYSTEM_OFF
boostSwitchRWHeats the cylinder once now

device ​

ChannelTypeRead/WriteDescription
current-powerNumber:PowerRCurrent electrical power (needs fetchMpc)
operation-timeNumber:TimeRTotal operation time in hours (needs fetchRts)
on-off-cyclesNumberRTotal number of starts (needs fetchRts)
water-pressureNumber:PressureRWater pressure measured by the device, if it has a sensor
heating-energy-efficiencyNumberRHeat generated per consumed electrical energy for heating today

In addition, the binding adds a Number:Energy channel with today's value for every energy value the device reports, named after value type and operation mode, e.g.

  • consumed-electrical-energy-heating, consumed-electrical-energy-domestic-hot-water, consumed-electrical-energy-cooling
  • heat-generated-heating, heat-generated-domestic-hot-water
  • earned-environment-energy-heating, earned-environment-energy-domestic-hot-water
  • consumed-primary-energy-heating (gas boilers)

Today means since midnight in the time zone of the system. Only linked energy channels are updated.

Actions ​

The actions are available for rules as actions.thingActions('myvaillant', '<thing UID>') (JavaScript) or getActions("myvaillant", "<thing UID>") (DSL).

system ​

ActionDescription
exportEnergyData(resolution, start, end, operationMode)Energy values of all devices as JSON, null on errors
setHoliday(start, end)Sets away mode, empty start means now, empty end the configured duration
cancelHoliday()Ends away mode
setCoolingForDays(start, end)Cools manually between start and end
cancelCoolingForDays()Ends manual cooling
refresh()Updates the system after the refresh delay

resolution is HOUR (at most 3 days per call), DAY (at most 60 days) or MONTH. start and end are dates like 2026-11-01, 2026-11-01 00:00:00 or ISO dates, without offset they are in the time zone of the system. operationMode limits the export to HEATING, DOMESTIC_HOT_WATER or COOLING; every device and value type costs one request, so limit it where possible.

The result is a JSON array with one entry per device:

json
[
  {
    "device": {
      "device_uuid": "...",
      "name": "aroTHERM plus",
      "device_type": "HEATPUMP",
      "type": "primary_heat_generator"
    },
    "data": [
      {
        "operation_mode": "HEATING",
        "energy_type": "CONSUMED_ELECTRICAL_ENERGY",
        "resolution": "DAY",
        "total_consumption": 33600.0,
        "data": [
          {
            "start_date": "2026-11-12T01:00:00+01:00",
            "end_date": "2026-11-13T01:00:00+01:00",
            "value": 33600.0
          }
        ]
      }
    ]
  }
]

Values are in Wh.

zone ​

ActionDescription
setQuickVeto(temperature, durationHours)Starts or changes a quick veto, empty duration uses quickVetoDurationInHours
cancelQuickVeto()Ends the quick veto
setManualModeSetpoint(temperature, type)Sets the manual mode setpoint, type HEATING (default) or COOLING
getTimeProgram(type)Time program as JSON, type heating (default) or cooling
setTimeProgram(type, timeProgram)Sets the time program from JSON in the format of getTimeProgram

Time programs contain the weekdays monday ... sunday, each with a list of slots with startTime and endTime in minutes after midnight and setpoint in °C.

dhw ​

ActionDescription
getTimeProgram()Hot water time program as JSON
setTimeProgram(timeProgram)Sets the hot water time program
getCirculationTimeProgram()Circulation pump time program as JSON
setCirculationTimeProgram(timeProgram)Sets the circulation pump time program

Full Example ​

demo.things ​

dsl
Bridge myvaillant:account:vaillant "myVAILLANT" [ username="user@example.com", password="secret", brand="vaillant", country="germany", refreshInterval=300, fetchRts=true, fetchMpc=true ] {
    Bridge system home "Heat Pump" [ systemId="0123456789abcdef" ] {
        Thing zone zone0 "Heat Pump Zone" [ index=0 ]
        Thing circuit circuit0 "Heat Pump Circuit" [ index=0 ]
        Thing device primary-heat-generator "Heat Pump" [ deviceUuid="..." ]
        Thing device electric-backup-heater "Backup Heater" [ deviceUuid="..." ]
    }
}

demo.items ​

dsl
Number:Temperature Outdoor_Temperature "Outdoor [%.1f °C]"         { channel="myvaillant:system:vaillant:home:outdoor-temperature" }
Number:Temperature Room_Target         "Target [%.1f °C]"          { channel="myvaillant:zone:vaillant:home:zone0:desired-room-temperature-setpoint" }
String             Heating_Mode        "Mode [%s]"                 { channel="myvaillant:zone:vaillant:home:zone0:operation-mode-heating" }
Number:Temperature Flow_Temperature    "Flow [%.1f °C]"            { channel="myvaillant:circuit:vaillant:home:circuit0:current-flow-temperature" }
Number:Power       HeatPump_Power      "Power [%d W]"              { channel="myvaillant:device:vaillant:home:primary-heat-generator:current-power" }
Number:Energy      HeatPump_Heating    "Heating today [%.1f kWh]"  { channel="myvaillant:device:vaillant:home:primary-heat-generator:consumed-electrical-energy-heating" }

demo.js ​

javascript
const vaillant = actions.thingActions(
  "myvaillant",
  "myvaillant:system:vaillant:home",
);
const json = vaillant.exportEnergyData(
  "DAY",
  "2026-11-01",
  "2026-11-20 23:59:59",
  "HEATING",
);
if (json !== null) {
  JSON.parse(json).forEach((device) =>
    console.info(device.device.name, device.data.length),
  );
}